LIEBERT INTELLISLOT® WEB/485 CARD WITH ADAPTER
Emerson Liebert IntelliSlot IS-WEB485ADPT User Manual Page 26. Open Internet Explorer and enter followed by the IP address or hostname of the Web. Card—for example, the address bar. The following message appears.
Product Specification/Installation Sheet
Description
The IntelliSlot Web/485 Card with Adapter provides 10/100baseT Ethernet Network and Modbus connectivity for your Emerson Network Power equipment.
Operating status is monitored and alarms are communicated via the network, using SNMP and/or HTTP protocols and over RS-485 using the Modbus protocol.
Additional Features
• SNMP v1, v2c with MIB-II support | • BootP, DHCP per RFC2131 |
• HTTP/HTTPS 1.1 | • Secure Sockets (SSL) |
• Telnet | • Remote firmware updates via HTTP |
Compatibility With Other Emerson Network Power Products
Precision Cooling Unit (Controller*) | *Controller Codes | Large UPS | ||
• | Liebert Challenger™ 3000 (L00, L15, | L00: Level 00 | • | Liebert Npower™ |
• | LSM, LAM) | L0B: Level 0B | • | Liebert Series 300™ |
Liebert DataMate™ (L0B) | L10: Level 10 | • Liebert Series 600™/610™ (Single Module) | ||
• Liebert Deluxe System/3™ (L10, L15, 16V DOHC Gasoline2.7L 6 Cyl. Description: (ID 1331 Sebring JR Dodge Stratus Factory Service ManualIncludes Manuals –2002 Sebring JR Dodge Stratus Factory Service Manual2002 Sebring JR Dodge Stratus Gas Powertrain Manual2002 Sebring JR Dodge Stratus Body Manual2002 Sebring JR Dodge Stratus Chassis Manual2002 Sebring JR Dodge Stratus Transmission ManualCovers Models –Sedan and ConvertibleStratusSebringHigh linePremiumSpecial5-Speed Manual4 Speed Automatic41TE/AE Electronic TransaxleConvertible / Open Body4 Door SedanEngines –2.0L 4 Cyl. 2002 dodge stratus repair manual free download. 16V DOHC Gasoline2.4L 4 Cyl. | • Liebert Series 610 System Control Cabinet | |||
L15: Level 15 | ||||
LSM, LAM) | (Multi-Module) | |||
• | Liebert Himod™ (LAM) | LSM: Standard | • | Hiross 7200 (EMEA) |
• | Liebert Industrial Cooling Series™ | Microprocessor | • | Hiross HiPulse™ (EMEA) |
(L10, LSM, LAM) | ||||
LAM: Advanced | Power Management | |||
• | Liebert Mini-Mate™ (L0B) | |||
Microprocessor | ||||
• | Liebert Datawave® | |||
• | Liebert Mini-Mate2™ (MM2) | |||
• | Liebert FPC™ | |||
• Liebert Mini-Mate2 8 Ton (L8T) | ||||
• Liebert Precision Power Center™ | ||||
• | Hiross™ Microface IGMnet | |||
• Liebert Static Transfer Switches: | ||||
• | PEC/Atlas™ (CEMS100/LECS15) | |||
STS™, STS2-3 pole, STS2/PDU |
Overall and Mounting Dimensions
7' (177.8mm) | |
0.6' (15.3mm) | |
2.8' | 3.4' |
(71.1mm) | (86.4mm) |
0.8' (20.3mm) | |
Six holes, each | 2.4' |
0.156' diameter | |
(61mm) | |
4' | |
(101.6mm) |
0.4' (10.2mm) 0.2' (5mm)
3.2'
(81.3mm)
Customer Wiring
Input power (input to TB3)
Pin 1(+)
Pin 2(-) Pin 3 (NC)
Modbus output for BMS
(output from TB2)
TB1: Pin 1 (+), Pin 2 (-)
TB2: Pin 1 (+), Pin 2 (-)
Network port for NMS and Web access
DTE serial port for configuration
(requires null-modem connection)
IGMnet or Liebert SiteScan® Comms from unit (input to TB1 or P1)
Refer to user manual for details
Specifications
Liebert Unity Card User Manual
Power | AC Inputs | 18 - 24 VAC; 50/60 Hz |
DC Inputs | 12 - 36VDC | |
Requirements | ||
Power Consumption | 6VA maximum | |
Dimensions - W x D x H: in. (mm) | 7 x 4 x 1.5 (178 x 102 x 38) | |
Weight | Net - oz. (kg) | 7 (0.2) |
Shipping - lb. (kg) | 1.3 (0.6) | |
Ambient Operating Environment, °F (°C) | 32 to 104 (0 to 40); 10% to 90% RH (non-condensing) | |
Ambient Storage Temperature, °F (°C) | -4 to 140 (-20 to 60) | |
Protection | SELV Isolated User Connections, Watchdog Timer Circuitry | |
Service Terminal (RS-232) | DB9F, DTE | |
Manual of acupuncture deadman pdf download. Communication | Unit Input | TB1, 2-Position Terminal Block |
Communications | P1, 20-PIN Vertical Header with Ejection Latches (for some UPS models) | |
Ports | ||
Modbus (RS-485) | TB2, 2-Position Terminal Block | |
Ethernet Communications | RJ45 |
Wiring Specifications
Connection | Supported Wire Types | Maximum Wire Length |
TB1 (RS-422) | 18-22 AWG Stranded & Shielded; 18 AWG* recommended | 1000 ft. (300m) |
Non Plenum - Belden 9461; Plenum - Belden 88761 | ||
TB2 (RS-485) | 18-22 AWG Stranded & Shielded; 18 AWG* recommended | 3000 ft. (915m) |
Non Plenum - Belden 9461; Plenum - Belden 88761 | ||
TB3 (Power Input) | 18-22 AWG Stranded & Shielded; 18 AWG* recommended | 20 ft. (6m) |
Non Plenum - Belden 8770; Plenum - Belden 88770 | ||
20-comm-e ethernet/ip adapter user manual. DB9F Connector | DTE Null Modem Cable | 50 ft. (15m) |
RJ45 Connector | Standard Category 5 Cable | 328 ft. (100m) |
Liebert Corporation
1050 Dearborn Drive | Telephone: 1-800-877-9222 |
P.O. Box 29186 | Facsimile: 1-614-841-6022 |
Columbus, OH 43229 | www.liebert.com |
© 2007 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-29105_REV02_10-07
To continue the download you need to go through the captcha: